- Product description
-
Product descriptionLSA basic protection magazine for use in multi-core data cable systems, MCR systems and telephone switchboards.
• Basic protection
• Equipped with 20 gas arresters
• Max. voltage: 180 V
Application: Directly on LSA-Plus separating strips or connection rails (e.g. OBO LSA-A-LEI (5084 00 8) or OBO LSA-T-LEI (5084 01 2).
Basic protection magazine to protect 10 two-cores.
- Technical data
-
Technical data
Cable type for surge protection devices Telecommunications line Capacity (wire-earth) < 10 pF Capacity (wire-wire) < 10 pF Dimension 180V Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs) Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs) Insulation resistance > 1 GΩ Kategorie Type 1+2 / D1+C2 Lightning impulse current 0,5 kA Lightning protection zone LPZ 0→2 Maximum continuous voltage AC 120 V Maximum continuous voltage DC 180 V Nominal load current AC 0,7 A Nominal load current DC 1 A Number of poles 20 Permitted temperature range, max. 80 °C Permitted temperature range, min. -40 °C Plug-in system Other Protection level @ C1 <750 V Protection rating IP20 SPD to IEC 61643-21 Class I+II / D1+C2 Testing standard IEC 61643-21 Total discharge current (10/350) 1 kA Total discharge current (8/20) 10 kA Version for Basic protection - All types
- Downloads
-
Data sheet LSA-B-MAG / 5084020 , 0.23MB , pdfEU declaration of conformity LSA-B-MAG / 5084020 , 0.06MB , pdfREACH Declaration of conformity LSA-B-MAG / 5084020 , 0.12MB , pdfRoHS Declaration of conformity LSA-B-MAG / 5084020 , 0.12MB , pdfTechnical information Technical information, LSA ... , 0.47MB , pdf
China - English